Skip to main content
Schneider Electric A9N18576

A9N18576 Vigi C120 Add-on RCD, 3P, 300 mA, Type A

MPN A9N18576
Obsolete

Schneider Electric Acti9 Vigi C120 add-on residual current device, A9N18576, 3P, 300 mA sensitivity, Type A, 125 A rated current, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N18576 specifications
ParameterValue
Main product or component typeAdd-on residual current device
Voltage230...415 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-1
IP ratingIP20
Temp storage max60 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...60 °C
Pollution degree3 conforming to IEC 60947-2
ColorWhite
Depth73 mm
Width171 mm
Height95 mm
Mechanical life cycles20000 cycles
Operating temperature-25...60 °C

Product details

The A9N18576 is a Schneider Electric Acti9 Vigi C120 add-on residual current device — a 3-pole, 300 mA sensitivity, Type A earth-leakage block rated for 125 A continuous current. It clips onto a 35 mm symmetrical DIN rail and connects to the upstream MCB via screw terminals, making it a straightforward retrofit in an existing Acti9 distribution board.

Rated current is 125 A, operational voltage 230…415 V AC. Sensitivity is 300 mA instantaneous trip. Type A detection covers sinusoidal AC residual currents plus pulsating DC residual currents up to 6 mA of smooth DC superimposed — the standard requirement for circuits with single-phase rectifiers or electronic loads. Pollution degree 3 (IEC 60947-2) means it tolerates conductive pollution in industrial panels where condensation or light dust is expected. The voltage-independent tripping technology means the RCD operates on fault current alone, without needing a separate power supply — it clears a ground fault even if the line voltage is lost. That is a reliability advantage for safety-critical feeders.

Integration notes

The block occupies 10 pitches of 9 mm each (90 mm total width on the rail). Tunnel-type terminals accept 1…50 mm² rigid or 1…35 mm² flexible conductors; strip length is 15 mm and tightening torque is 3.5 N·m.

MPN