Schneider Electric A9N18599 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N18599 Acti9 Vigi C120 RCD, 4P 125A A-S

MPNA9N18599
Active

Schneider Electric Acti9 Vigi C120 add-on residual current device, 4P, 125A, Type A-SI (Super Immunised), 500 mA, instantaneous, 230…415 VAC.

$642.06Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9N18599 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)500 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9N18599 — Electrical Ratings
ParameterValue
Rated current (In)125 A
Rated operational voltage (Ue)230...415 V AC 50 Hz
Poles description4P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-1
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer Group incomer
Mechanical durability (operating cycles)20000 cycles
A9N18599 — Identification
ParameterValue
Product nameActi9 Vigi C120
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi C120
A9N18599 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Width in 9 mm modules10
Terminal connectionsTunnel type terminals 1...35 mm² flexible Tunnel type terminals 1...50 mm² rigid
Wire stripping length15 mm
Terminal tightening torque3.5 N.m
Width198 mm
Height95 mm
Depth73 mm
A9N18599 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...60 °C
IP degree of protectionIP20
Pollution degree3 conforming to IEC 60947-2
A9N18599 — Approvals
ParameterValue
StandardsEN 61009 IEC/EN 61009-2-1

Product details

The Schneider Electric A9N18599 is an add-on residual current device (RCD) from the Acti9 Vigi C120 range. It is a 4-pole unit rated for 125 A continuous current, with a 500 mA earth-leakage sensitivity and Type A-SI (Super Immunised) protection class. Rated operational voltage is 230…415 V AC at 50 Hz, with an insulation voltage of 500 V AC and impulse withstand of 6 kV per IEC 60947-2. The trip is instantaneous — no intentional time delay — so it clears ground faults immediately, which matters for personnel protection in a panel where you want fast disconnect on the outgoing group.

The unit occupies 10 modules of 9 mm pitch — that is 198 mm of rail width. Depth is 73 mm, height 95 mm. Plan for that footprint when laying out a distribution board; it is a wide unit at 4P, so check your enclosure fill factor. Electrical connection to the upstream MCB is by screws. Terminals accept 1…35 mm² flexible or 1…50 mm² rigid cable.

Designed to EN 61009 and IEC/EN 61009-2-1. Ambient operating range is -25…60 °C; storage range -40…60 °C.

Frequently asked questions

Where can I buy the A9N18599 and get a price?

The A9N18599 is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the A9N18599's rated current and earth-leakage sensitivity?

Rated current is 125 A. Earth-leakage sensitivity is 500 mA, Type A-SI (Super Immunised), instantaneous trip.

What compliance standards does the A9N18599 meet?

It complies with EN 61009 and IEC/EN 61009-2-1. Pollution degree 3 per IEC 60947-2. Rated insulation voltage 500 V AC, impulse withstand 6 kV.

MPN
A9N18599