Skip to main content
Schneider Electric A9N19304 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N19304 DPN Vigi RCBO, Type A, 10 A, 10

MPNA9N19304
Obsolete

Schneider Electric Acti9 DPN Vigi, RCBO, 1P+N, Type A, 10 A, 10 mA, C-curve, 6 kA, DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N19304 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9N19304 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 30 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC conforming to EN 61009
Rated impulse withstand voltage (Uimp)4 kV conforming to EN 61009
Device location in systemOutgoer
Electrical durability20000 cycles conforming to IEC 61009
Mechanical durability (operating cycles)20000 cycles
A9N19304 — Identification
ParameterValue
Product nameDPN Vigi
Product / component typeEarth leakage circuit breaker
Product range / familyActi9
Device short nameDPNa Vigi
A9N19304 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals16 mm² rigid Tunnel type terminals10 mm² flexible
A9N19304 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...60 °C
Pollution degree3 conforming to EN 61009
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2 conforming to EN 61009
A9N19304 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1 EN/IEC 61009-1

Product details

The Schneider Electric A9N19304 is an Acti9 DPN Vigi residual current circuit breaker with overcurrent protection (RCBO) in a 1P+N format — it combines a thermal-magnetic MCB and a voltage-independent earth leakage module in one 4-module wide (9 mm per pitch) DIN-rail unit. The 10 A rated current (In) at 30 °C and C-curve magnetic trip (5 to 10 x In) mean it's sized for general-purpose socket circuits and small lighting loads where moderate inrush from capacitive or motor-start loads is expected. The 10 mA earth leakage sensitivity (Type A) detects sinusoidal AC and pulsating DC residual currents, which covers most modern electronics and variable-speed drive leakage profiles.

The toggle provides local ON/OFF indication and a contact position indicator. Pollution degree 3 and tropicalisation class 2 per EN 61009 mean it's rated for environments with conductive pollution and high humidity (95 % at 55 °C) — suitable for installation in non-conditioned enclosures. Operating altitude is rated to 2000 m without derating.

The voltage-independent residual current tripping technology means the earth leakage protection operates even if the line voltage is lost — a key safety feature for fault detection on a dead circuit. Electrical and mechanical durability are both rated at 20,000 cycles per IEC 61009.

Frequently asked questions

Where can I buy the A9N19304?

The A9N19304 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What does the Type A classification mean on this RCBO?

Type A residual current detection means the device trips on sinusoidal AC faults and pulsating DC faults up to 10 mA — covering leakage from rectified loads, VFDs, and switched-mode power supplies commonly found in modern electrical installations.

What is the breaking capacity of the A9N19304?

The breaking capacity is 6 kA Icn at 230 V AC 50/60 Hz per EN 61009, suitable for final subcircuits in distribution boards with adequate upstream fault current limitation.

What is the closest alternative to the A9N19304 in the Acti9 range?

Within the Acti9 DPN Vigi family, the main variant differences are rated current (In) and earth leakage sensitivity (IΔn). The A9N19304 is the 10 A, 10 mA Type A version. A higher-current sibling (e.g., 16 A or 20 A) or a 30 mA sensitivity variant would be the natural alternative if the load or protection requirements differ — but the physical footprint and terminal capacity remain the same across the range.

MPN