Specifications

A9N19532 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9N19532 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9N19532 — Identification
ParameterValue
Product nameActi9 DPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameDPNa Vigi
A9N19532 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height81 mm
Depth77.5 mm
A9N19532 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity90 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N19532 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9N19532 is an Acti9 DPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — a single-module (36 mm wide) device combining a 10 A thermal-magnetic MCB with a 30 mA earth-leakage trip in one 1P+N package. The C-curve (magnetic trip 5–10 x In) handles moderate inrush from lighting or small motor loads without nuisance trips, while the integrated 30 mA residual-current element provides personal protection against earth faults.

Rated current In = 10 A, so it protects a final subcircuit drawing up to 10 A continuous — typical for lighting banks, socket outlets, or small appliances. Breaking capacity Icn = 4500 A at 220–240 V AC, 50/60 Hz, per EN/IEC 61009-2-1. If your site's available fault current exceeds 4.5 kA, you need a higher-rated upstream breaker or a current-limiting device to coordinate. Earth-leakage sensitivity is fixed at 30 mA — the standard threshold for personal protection against indirect contact. The device trips on both overcurrent (thermal-magnetic) and residual current, so it replaces two separate units (MCB + RCCB) in one DIN-rail slot. IP20 on the device body, IP40 inside the modular enclosure — suitable for dry indoor panels, not washdown environments.

Tropicalisation level 2 per IEC 60068-1 indicates the device withstands damp heat conditions typical of non-air-conditioned electrical rooms. The manufacturer provides CE declaration of conformity and, for EU markets, the UKCA marking. RoHS and REACH compliance documentation is available from Schneider Electric's product support pages — the paperwork is clean for cross-border shipments.

Frequently asked questions

Where can I buy A9N19532 and get a price?

The A9N19532 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a landed-cost figure.

What is the breaking capacity of A9N19532?

The breaking capacity is 4500 A Icn at 220–240 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1.

What compliance documentation does Schneider provide for A9N19532?

The device carries CE and UKCA marking, is tested to EN/IEC 61009-2-1, and meets tropicalisation level 2 per IEC 60068-1. RoHS and REACH declarations are available from Schneider Electric's documentation portal.

MPN