The Type A-SI (Super Immunised) designation means the residual-current detection is filtered against nuisance tripping from high-frequency leakage currents common on VFD-fed or switched-mode power-supply circuits, while still catching the 50/60 Hz sinusoidal and pulsating DC faults a standard Type A device would. The 40 A rated current (In) at 30 °C and C-curve magnetic trip (5–10 x In) handle general-purpose loads like lighting, socket outlets, and small motor circuits; the 30 mA earth-leakage sensitivity provides personal protection per IEC 61009.
IP20 on the body, IP40 inside a modular enclosure.