Skip to main content
Schneider Electric A9N19643 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N19643 DPN Vigi RCBO, Type A-SI, 13 A,

MPNA9N19643
Obsolete

Schneider Electric Acti9 DPN Vigi, Type A-SI (Super Immunised) RCBO, 1P+N, 13 A, C-curve, 30 mA earth leakage, 6 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N19643 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9N19643 — Electrical Ratings
ParameterValue
Rated current (In)13 A at 30 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC conforming to EN 61009
Rated impulse withstand voltage (Uimp)4 kV conforming to EN 61009
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability20000 cycles conforming to IEC 61009
Mechanical durability (operating cycles)20000 cycles
A9N19643 — Identification
ParameterValue
Product nameDPN Vigi
Product / component typeEarth leakage circuit breaker
Product range / familyActi9
Device short nameDPN N Vigi
A9N19643 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid
A9N19643 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...60 °C
Pollution degree3 conforming to EN 61009
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2 conforming to EN 61009
A9N19643 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

Rated 13 A at 30 °C with a C-curve magnetic trip (5–10 × In) and 300 mA earth-leakage sensitivity, it breaks up to 6000 A Icn at 230 V AC per EN/IEC 61009. The Type A-SI (Super Immunised) designation means it resists nuisance tripping from high-frequency leakage currents common on modern electronic loads — switched-mode power supplies, VFDs, LED drivers — that would trip a standard Type A device.

Snaps onto standard DIN rail (mounting support per). Occupies 4 × 9 mm pitches — a single 36 mm width — so it fits a compact outgoer position in a residential or light-commercial distribution board. Embedding depth is 72 mm, leaving clearance behind the gland plate in a standard 100 mm enclosure.

Frequently asked questions

What is A9N19643's listed type (Type A-SI (Super Immunised))?

The A9N19643 is a Type A-SI (Super Immunised) RCBO, meaning it is designed to resist nuisance tripping from high-frequency leakage currents generated by electronic loads like switched-mode power supplies and VFDs.

How do I get current pricing and availability for A9N19643?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels — no automated price or stock count is displayed here.

What compliance documentation does this brand provide for A9N19643?

The A9N19643 is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. It carries a pollution degree 3 rating and overvoltage category III per those standards. For RoHS/REACH declarations, refer to the manufacturer's documentation portal using the order code.

MPN