Its 25 A rated current (In) at 30 °C and C-curve magnetic trip (5...10 x In) suit it for general-purpose distribution circuits feeding socket outlets or mixed resistive-inductive loads where moderate inrush is expected. The 300 mA earth-leakage sensitivity and Type A-SI (Super Immunised) classification mean it tolerates high-frequency leakage from VFDs, UPS systems, or LED drivers without nuisance tripping — a key consideration on modern panels where switched-mode power supplies are common. The thermal-magnetic trip unit provides both overload and short-circuit protection on the phase conductor only, with the neutral switched but not protected.
Deployment context
Mounts on DIN rail (4 x 9 mm pitches) and occupies a single module width, making it a space-efficient choice for final sub-circuits in Acti9 distribution boards.
Limitation class 3 per EN 61009 indicates energy-limiting performance that aids downstream selectivity. Operating altitude is 2000 m.