It combines a 20 A thermal-magnetic trip (C-curve, 5...10 x In magnetic threshold) with integrated 30 mA Type AC earth-leakage detection in a single 4-module (9 mm pitch) DIN-rail unit.
Mounts on DIN rail with neutral on the left side. The toggle provides local ON/OFF indication, and the contact position indicator confirms the state of the main contacts without needing to open the panel.
The voltage-independent residual current trip operates instantaneously at 30 mA sensitivity, providing supplementary protection against direct contact. Electrical and mechanical durability are both rated at 20,000 cycles per IEC 61009.