Schneider Electric A9N19667 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N19667 DPN N Vigi RCBO, 25 A, 30 mA, Ty

MPNA9N19667
Active

Schneider Electric Acti9 DPN N Vigi RCBO, Type AC, 25 A, 30 mA, C-curve, 6 kA Icn at 230 V AC, 1P+N, DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N19667 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9N19667 — Electrical Ratings
ParameterValue
Rated current (In)25 A at 30 °C
Rated operational voltage (Ue)230 V AC
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Rated insulation voltage (Ui)400 V AC conforming to EN 61009
Rated impulse withstand voltage (Uimp)4 kV conforming to EN 61009
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability10000 cycles conforming to IEC 61009
Mechanical durability (operating cycles)20000 cycles
A9N19667 — Identification
ParameterValue
Product nameDPN Vigi
Product / component typeEarth leakage circuit breaker
Product range / familyActi9
Device short nameDPN N Vigi
A9N19667 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid
A9N19667 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...60 °C
Pollution degree3 conforming to EN 61009
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2 conforming to EN 61009
A9N19667 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The Schneider Electric A9N19667 is a DPN N Vigi RCBO from the Acti9 range — a combined overcurrent and residual-current device in a single 1P+N module. Rated 25 A at 30 °C with a C-curve magnetic trip (5–10 × In) and 30 mA Type AC earth-leakage protection, it handles final subcircuits in residential and light commercial distribution boards.

That covers standard resistive and inductive loads (heaters, lighting, motors) but not variable-speed drives, UPS outputs, or LED drivers that can generate non-sinusoidal leakage. The C-curve (5–10 × In) holds through moderate inrush from motor-starting or capacitive loads, so it's a general-purpose choice for socket-outlet circuits and small appliances. Rated operational voltage is 230 V AC single-phase, with insulation rated to 400 V AC.

Snaps onto standard DIN rail (mounting support: DIN rail). The toggle switch gives local ON/OFF indication. Relative humidity tolerance 95 % at 55 °C. Altitude limit 2000 m.

Frequently asked questions

What is the breaking capacity of A9N19667?

6 kA Icn at 230 V AC conforming to EN 61009.

What type of earth-leakage protection does this RCBO provide?

Type AC — detects sinusoidal AC residual currents only, with 30 mA sensitivity and instantaneous time delay.

Where can I buy A9N19667?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What standards does A9N19667 comply with?

EN/IEC 61009-1 and EN/IEC 61009-2-1 — the harmonized standards for RCBOs (residual current operated circuit-breakers with integral overcurrent protection).