Skip to main content
Schneider Electric A9N19668 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N19668 DPN N Vigi 32A Type AC RCBO, 30m

MPNA9N19668
Active

Schneider Electric Acti9 DPN N Vigi RCBO, 1P+N, 32 A, 30 mA Type AC, C curve, 6 kA, 230 V AC.

$70.06Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N19668 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9N19668 — Electrical Ratings
ParameterValue
Rated current (In)32 A at 30 °C
Rated operational voltage (Ue)230 V AC
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Rated insulation voltage (Ui)400 V AC conforming to EN 61009
Rated impulse withstand voltage (Uimp)4 kV conforming to EN 61009
Overvoltage categoryIV
Device location in systemOutgoer
Electrical durability10000 cycles conforming to IEC 61009
Mechanical durability (operating cycles)20000 cycles
A9N19668 — Identification
ParameterValue
Product nameDPN Vigi
Product / component typeEarth leakage circuit breaker
Product range / familyActi9
Device short nameDPN N Vigi
A9N19668 — Mechanical
ParameterValue
Mounting support35 mm DIN rail
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals (top or bottom) 1 cable(s) 1...10 mm² flexible with ferrule Tunnel type terminals (top or bottom) 1 cable(s) 1...16 mm² rigid
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height81 mm
Depth77.5 mm
A9N19668 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN 61009
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2 conforming to IEC 60068-1
A9N19668 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

What this RCBO covers

It combines a 32 A thermal-magnetic MCB (C curve) with integrated 30 mA Type AC earth-leakage protection in a single 1P+N module, 36 mm wide. Type AC detection means it trips on sinusoidal AC residual currents only — the standard choice for general socket-outlet, lighting, and heater circuits where no pulsed or DC fault content is expected. The 30 mA sensitivity provides personal protection against direct-contact earth faults, while the C curve (magnetic trip at 5 to 10 x In) handles moderate inrush from small motor or capacitive loads without nuisance tripping. Mounts on a 35 mm DIN rail, occupies 4 x 9 mm pitches (36 mm total width), and accepts tunnel terminals for 1 to 16 mm² rigid or 1 to 10 mm² flexible cable. The white enclosure carries ON/OFF local signalling and a toggle control.

Limitation class 3 per EN 61009, tropicalisation class 2 per IEC 60068-1, and IP20 (IP40 in modular enclosure) per IEC 60529. The 10,000-cycle electrical durability and 20,000-cycle mechanical durability are per IEC 61009.

Frequently asked questions

What is the A9N19668's type and sensitivity?

It is a Type AC residual-current device with 30 mA sensitivity, meaning it detects sinusoidal AC earth-leakage currents only. This suits general-purpose socket and lighting circuits without pulsed DC fault content.

Where can I buy the A9N19668 and how is it quoted?

The A9N19668 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What cable sizes fit the A9N19668 terminals?

The tunnel-type terminals accept 1 to 16 mm² rigid cable or 1 to 10 mm² flexible cable with ferrule, top or bottom connection. Wire stripping length is 15 mm and tightening torque is 2 N.m.

MPN