What this RCBO covers
It combines a 32 A thermal-magnetic MCB (C curve) with integrated 30 mA Type AC earth-leakage protection in a single 1P+N module, 36 mm wide. Type AC detection means it trips on sinusoidal AC residual currents only — the standard choice for general socket-outlet, lighting, and heater circuits where no pulsed or DC fault content is expected. The 30 mA sensitivity provides personal protection against direct-contact earth faults, while the C curve (magnetic trip at 5 to 10 x In) handles moderate inrush from small motor or capacitive loads without nuisance tripping. Mounts on a 35 mm DIN rail, occupies 4 x 9 mm pitches (36 mm total width), and accepts tunnel terminals for 1 to 16 mm² rigid or 1 to 10 mm² flexible cable. The white enclosure carries ON/OFF local signalling and a toggle control.
Limitation class 3 per EN 61009, tropicalisation class 2 per IEC 60068-1, and IP20 (IP40 in modular enclosure) per IEC 60529. The 10,000-cycle electrical durability and 20,000-cycle mechanical durability are per IEC 61009.