Schneider Electric A9N19753 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N19753 Acti9 DPN Vigi RCBO, 6 A, B Curv

MPNA9N19753
Obsolete

Schneider Electric Acti9 DPN Vigi RCBO, A9N19753, 6 A, B curve, 1P+N, 6000 A breaking capacity, integrated earth leakage, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N19753 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9N19753 — Electrical Ratings
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9N19753 — Identification
ParameterValue
Product nameActi9 DPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameDPN N Vigi
A9N19753 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height81 mm
Depth77.5 mm
A9N19753 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity90 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N19753 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9N19753 is an Acti9 DPN Vigi RCBO — a combined miniature circuit breaker and residual-current device in a single 36 mm wide module, 1P+N poles, rated 6 A with a B curve and integrated earth-leakage protection.

The 6 A rated current (In) is the continuous load the RCBO can carry without tripping — sized for a final subcircuit like lighting or socket outlets. The B curve means magnetic tripping occurs at 3 to 5 times In (18 to 30 A), so it clears short-circuits quickly while tolerating the inrush of resistive loads. The thermal-magnetic trip unit handles overloads (thermal) and short-circuits (magnetic) in one mechanism. Integrated earth-leakage protection (RCD function) saves one module width compared to a separate MCB + RCD pair — the 36 mm width is a single 4-pitch module on a 9 mm pitch DIN rail.

Mounting and wiring notes

Clip-on mounting to DIN rail, neutral on the left. Tunnel-type terminals accept 0.75 to 16 mm² rigid or 0.33 to 10 mm² flexible (with or without ferrule). The 9 mm pitch between phase and neutral matches the standard Acti9 busbar spacing — no adapters needed for horizontal distribution.

Frequently asked questions

What is the breaking capacity of the A9N19753?

6000 A Icn at 220–240 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1.

Where can I buy the A9N19753?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation is available for the A9N19753?

The part is certified to EN/IEC 61009-2-1, with tropicalisation class 2 per IEC 60068-1. IP20 (finger-safe) and IP40 (modular enclosure) per IEC 60529. Overvoltage category III per IEC 60364.

MPN