Rated 16 A with a B curve (magnetic trip 3–5 x In), it delivers 6000 A breaking capacity at 230/240 V AC, per EN/IEC 61009-2-1. The integrated earth-leakage protection eliminates the need for a separate RCCB, saving one DIN-rail slot in the panel.
Clip-on mounting to DIN rail (35 mm per EN 60715). The 1P+N format places the neutral on the left; connection pitch is 9 mm between phase and neutral. IP20 on the body, IP40 inside a modular enclosure — suitable for distribution boards and final subcircuits.
Limitation class 3 (energy-limiting) per EN/IEC 61009-2-1 means it restricts let-through energy under fault conditions, improving downstream device coordination.