Skip to main content
Schneider Electric A9N19777 — Residual Current Breakers (RCCB/RCBO)

A9N19777 Acti9 DPN Vigi RCBO 25 A C-curve 6 kA 1P+N

MPNA9N19777
Obsolete

Schneider Electric Acti9 DPN Vigi RCBO, 25 A, C-curve, 6 kA Icn, 1P+N, integrated earth-leakage, DIN rail mount, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N19777 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9N19777 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9N19777 — Identification
ParameterValue
Product nameActi9 DPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameDPN N Vigi
A9N19777 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height81 mm
Depth77.5 mm
A9N19777 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity90 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9N19777 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The A9N19777 is a 1P+N RCBO from the Acti9 DPN Vigi family — a combined overcurrent and earth-leakage device in a single 36 mm wide module. Integrated earth-leakage protection means this single unit replaces both a MCB and a separate RCCB — saving a DIN-rail slot and reducing wiring. Clip-on mounting onto standard DIN rail, tunnel terminals accepting up to 16 mm² rigid, and a white modular enclosure rated IP20 (IP40 inside the panel) make it a straightforward swap-in for a failed or undersized RCBO on an outgoer.

Frequently asked questions

How do I get current pricing and availability for A9N19777?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is A9N19777's rated current and breaking capacity?

Rated current is 25 A with a C-curve. Breaking capacity is 6000 A Icn at 220...240 V AC, 50/60 Hz, per EN/IEC 61009-2-1.

Does A9N19777 include earth-leakage protection?

Yes, earth-leakage protection is integrated into the device, so it functions as a combined RCBO (overcurrent + residual current) in one module.

MPN
A9N19777