The A9N19777 is a 1P+N RCBO from the Acti9 DPN Vigi family — a combined overcurrent and earth-leakage device in a single 36 mm wide module. Integrated earth-leakage protection means this single unit replaces both a MCB and a separate RCCB — saving a DIN-rail slot and reducing wiring. Clip-on mounting onto standard DIN rail, tunnel terminals accepting up to 16 mm² rigid, and a white modular enclosure rated IP20 (IP40 inside the panel) make it a straightforward swap-in for a failed or undersized RCBO on an outgoer.
A9N19777 Acti9 DPN Vigi RCBO 25 A C-curve 6 kA 1P+N
MPNA9N19777
Obsolete
Schneider Electric Acti9 DPN Vigi RCBO, 25 A, C-curve, 6 kA Icn, 1P+N, integrated earth-leakage, DIN rail mount, white.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Earth-leakage sensitivity (IΔn) | 30 mA |
| Earth-leakage protection class / type | Type A |
| Earth-leakage trip time delay | Instantaneous |
| Residual-current tripping technology | Voltage independent |
| Trip unit technology | Thermal-magnetic |
| Local signalling / indication | ON, OFF, fault trip |
| Parameter | Value |
|---|---|
| Rated current (In) | 25 A |
| Rated operational voltage (Ue) | 220...240 V AC 50/60 Hz |
| Poles description | 1P + N |
| Neutral pole position | Left |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Rated insulation voltage (Ui) | 400 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Overvoltage category | III conforming to IEC 60364 |
| Device location in system | Outgoer |
| Electrical durability | 10000 cycles |
| Mechanical durability (operating cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| Product name | Acti9 DPN Vigi |
| Product / component type | Residual current breaker with overcurrent protection (RCBO) |
| Product range / family | Acti9 |
| Device short name | DPN N Vigi |
| Parameter | Value |
|---|---|
| Mounting support | DIN rail |
| Mounting mode | Clip-on |
| Control type | Toggle |
| Width in 9 mm modules | 4 |
| Terminal connections | Tunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule |
| Wire stripping length | 15 mm for top or bottom connection |
| Terminal tightening torque | 2 N.m top or bottom |
| Width | 36 mm |
| Height | 81 mm |
| Depth | 77.5 mm |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...60 °C |
| Storage ambient temperature | -30...70 °C |
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 |
| Relative humidity | 90 % at 55 °C |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 61009-2-1 |
Product details
Frequently asked questions
How do I get current pricing and availability for A9N19777?
Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.
What is A9N19777's rated current and breaking capacity?
Rated current is 25 A with a C-curve. Breaking capacity is 6000 A Icn at 220...240 V AC, 50/60 Hz, per EN/IEC 61009-2-1.
Does A9N19777 include earth-leakage protection?
Yes, earth-leakage protection is integrated into the device, so it functions as a combined RCBO (overcurrent + residual current) in one module.
MPN