It protects a 1P+N final circuit against overload, short-circuit (thermal-magnetic trip, C-curve, magnetic tripping limit 5...10 x In), and earth leakage (integrated 30 mA RCD). Rated 40 A with a breaking capacity of 6000 A Icn at 220...240 V AC, it is built to EN/IEC 61009-2-1, limitation class 3.
Clip-on mounting on DIN rail, 4 x 9 mm pitches wide (36 mm). Neutral on the left. Tunnel terminals accept 0.75...16 mm² rigid or 0.33...10 mm² flexible, tightening torque 2 N·m. IP20 on the body, IP40 inside a modular enclosure — suitable for distribution boards and final-subdistribution panels.