Skip to main content
Schneider Electric A9N19816 — 1-Pole MCB (DIN Rail)

Schneider Electric A9N19816 Acti9 C120H MCB, 100A 1P C Curve

MPNA9N19816
Obsolete

Schneider Electric Acti9 C120H, miniature circuit breaker, 100 A, 1 pole, C curve, 10 kA breaking capacity, A9N19816.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N19816 — Identification
ParameterValue
Product nameC120
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameC120H
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N19816 — Electrical & Protection
ParameterValue
Rated current (In)100 A at 30 °C
Rated operational voltage (Ue)230 V
Tripping curve codeC
Magnetic tripping limit5...10 x In conforming to GB/T 10963.1 8 x In +/- 20 % conforming to GB/T 14048.2
Breaking capacity (Icu / AIR)10 kA Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icn at 230 V AC 50/60 Hz conforming to GB/T 10963.1 10 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 230 V AC 50/60 Hz conforming to GB/T 14048.2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N19816 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals top or bottom 1...50 mm² rigid without cable end Tunnel type terminals top or bottom 1.5...35 mm² flexible with or without cable end
Mounting supportDIN rail
Mounting modeClip-on
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m
A9N19816 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
A9N19816 — Approvals
ParameterValue
Conformity standardsGB 10963.1 EN/IEC 60898-1 GB/T 14048.2 EN/IEC 60947-2
A9N19816 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV

Product details

The Schneider Electric A9N19816 is a miniature circuit breaker from the Acti9 C120H range, rated 100 A at 30 °C, single-pole, with a C curve and a breaking capacity of 10 kA Icn/Icu at 230 V AC.

The breaker is certified to GB 10963.1, EN/IEC 60898-1, GB/T 14048.2, and EN/IEC 60947-2. The dual standard means it meets both the household (60898-1) and industrial (60947-2) requirements — useful when the same panel must satisfy both a local code and an end-client's specification. The 6 kV impulse withstand voltage (Uimp) and 500 V rated insulation voltage (Ui) confirm it handles typical transient overvoltages in a 230/400 V network.

Panel integration

Tunnel terminals accept up to 50 mm² rigid or 35 mm² flexible cable. The toggle provides local ON/OFF indication and a contact-position indicator confirms the state for isolation — the breaker is marked suitable for isolation per the standards.

Frequently asked questions

Where can I buy A9N19816?

The A9N19816 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of A9N19816?

The A9N19816 has a breaking capacity of 10 kA Icn/Icu at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1 and EN/IEC 60947-2.

What standards does A9N19816 comply with?

It complies with GB 10963.1, EN/IEC 60898-1, GB/T 14048.2, and EN/IEC 60947-2.

MPN