The Schneider Electric A9N19821 is an Acti9 C120H miniature circuit breaker rated 100 A at 30 °C, with a D tripping curve (magnetic trip between 10 and 14 times In). The 10 kA breaking capacity at 400 V AC (Icn per IEC 60898-1, Icu per IEC 60947-2) is enough for most distribution panels fed from a 400 V transformer; it safely interrupts a fault up to that level without welding contacts or cascading upstream. Two poles protected, clip-on DIN rail mount, IP20 finger-safe enclosure — standard panel integration.
Complies with GB 10963.1, EN/IEC 60898-1, GB/T 14048.2, and EN/IEC 60947-2. Pollution degree 3 per IEC 60947-2, limitation class 3 per IEC 60898-1. Impulse withstand voltage 6 kV.
Tunnel-type terminals accept 1 to 50 mm² rigid (no ferrule) or 1.5 to 35 mm² flexible with or without ferrule. Tightening torque: 3.5 N·m on the power circuit. Strip length: 14 mm. The 9 mm pitch across 6 modules means it occupies 54 mm of DIN rail width — plan your enclosure fill factor accordingly.