Schneider Electric A9N19847 — Miniature Circuit Breakers (MCB)

A9N19847 Acti9 C120L MCB, 80A 4P D-curve, 15kA

MPNA9N19847
Obsolete

Schneider Electric Acti9 C120L miniature circuit breaker, A9N19847, 80 A 4P D-curve, 15 kA breaking capacity at 400 V AC, DIN-rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N19847 — Identification
ParameterValue
Product nameC120
Product rangeActi9
Product range (series)Acti9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N19847 — Ratings
ParameterValue
Rated current (In)80 A at 30 °C
Poles configuration4P
Number of protected poles4
Breaking capacity15 kA Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 15 kA Icn at 400 V AC 50/60 Hz conforming to GB/T 10963.1 15 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400 V AC 50/60 Hz conforming to GB/T 14048.2
Rated operational voltage (Ue)400 V
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N19847 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit10...14 x In conforming to GB/T 10963.1 12 x In +/- 20 % conforming to GB/T 14048.2
Suitability for isolationYes
Electrical durability (cycles)5000 cycles
Mechanical durability (cycles)20000 cycles
A9N19847 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals top or bottom 1...50 mm² rigid without cable end Tunnel type terminals top or bottom 1.5...35 mm² flexible with or without cable end
Terminal tightening torquePower circuit: 3.5 N.m
Wire stripping lengthPower circuit: 14 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Height81 mm
Depth73 mm
Number of 9 mm pitches12
A9N19847 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
A9N19847 — Approvals
ParameterValue
StandardsGB 10963.1 EN/IEC 60898-1 GB/T 14048.2 EN/IEC 60947-2

Product details

The A9N19847 is a Schneider Electric Acti9 C120L miniature circuit breaker, 80 A rated current at 30 °C, 4 poles, D curve, with a 15 kA breaking capacity at 400 V AC — that's the Icn per EN/IEC 60898-1 and the Icu per EN/IEC 60947-2, so it's rated for both residential and industrial fault-clearing duty. Clip-on to standard DIN rail, 12 module pitches wide (9 mm each, so 108 mm), with tunnel terminals accepting up to 50 mm² rigid or 35 mm² flexible.

80 A at 30 °C is the continuous rating — that's the current it can carry without tripping in a 30 °C ambient. That's a solid SCCR for a distribution board fed by a transformer of typical impedance. Dual-standard compliance (EN/IEC 60898-1 for household-type MCBs and EN/IEC 60947-2 for industrial breakers) means it's accepted in both residential and commercial/industrial panels — one part for mixed-duty installations.

Panel integration

Clip-on DIN-rail mount, 12 module positions (108 mm wide), 81 mm tall, 73 mm deep — fits standard distribution boards and sub-panels. Toggle actuator with ON/OFF local indication. Accepts 1–50 mm² rigid or 1.5–35 mm² flexible — covers most panel wiring from subfeed to load conductors.

Frequently asked questions

Where can I buy the A9N19847?

The A9N19847 is sourced through independent distribution channels — new-old-stock or verified surplus. We can quote it to order against an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9N19847?

15 kA Icn per EN/IEC 60898-1 and 15 kA Icu per EN/IEC 60947-2, both at 400 V AC 50/60 Hz — so it's rated for both residential and industrial fault levels.

What does the D curve mean on this breaker?

D-curve magnetic trip operates at 10–14× In, designed for loads with high inrush current like motors, transformers, or discharge lighting — prevents nuisance tripping on startup.

What standards does the A9N19847 comply with?

It complies with GB 10963.1, EN/IEC 60898-1, GB/T 14048.2, and EN/IEC 60947-2 — covering both household-type and industrial circuit-breaker standards.

MPN