The Schneider Electric A9N1P02DIN is an Acti9 xC60 miniature circuit-breaker rated 2 A with a D tripping curve, single pole, designed for clip-on mounting on 35 mm DIN rail in distribution panels. The D curve means magnetic tripping occurs at 12 x In (±20 %), so it handles inrush from motor or transformer loads without nuisance trips — the right choice for a 2 A branch feeding a small motor or solenoid bank. Breaking capacity is 10 kA Icu at 220–240 V AC (50/60 Hz) per IS/IEC 60947-2, with 15 kA at 12–48 V DC and 6 kA at 60 V DC — sufficient for most sub-distribution fault levels in industrial and commercial panels.
It carries IS/IEC 60947-2 certification, pollution degree 3, overvoltage category IV, and suitability for isolation — approvals that cover most industrial and commercial installations across IEC-adopting markets.
Width is 18 mm (2 x 9 mm pitches), so it occupies one standard DIN-rail module — important for panel fill-factor planning when packing multiple poles into a row. IP20 finger-safe front, tropicalisation class 2 per IEC 60068-1, and 95 % RH at 55 °C — suitable for enclosed distribution boards in humid or warm environments.