Schneider Electric A9N1P04DGN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P04DGN Acti9 xC60 MCB, 4A D Curve, 1P

MPNA9N1P04DGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P04DGN, 1P, 4 A rated, D curve, 10 kA breaking capacity at 240 V AC, clip-on for 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P04DGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P04DGN — Electrical & Protection
ParameterValue
Rated current (In)4 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P04DGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P04DGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P04DGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P04DGN is a 1-pole miniature circuit breaker from the Acti9 xC60 range, rated 4 A with a D tripping curve. It clips onto a standard 35 mm DIN rail inside a distribution board — the 18 mm width (2 x 9 mm pitches) matches the modular grid of a residential or light commercial panel. The D curve means its magnetic trip operates at 10 to 14 times the rated current (40 to 56 A instantaneous), which is the right characteristic for loads with a high inrush — think small transformers, solenoid valves, or motor starters where a B or C curve would nuisance-trip on startup. For a 4 A device, that inrush tolerance is the main selection criterion.

Breaking capacity and standards

Rated breaking capacity is 10,000 A Icn at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1 covers damp heat; the 95 % RH at 55 °C rating confirms it holds up in high-humidity environments without internal tracking.

Termination and wiring

The IP20 finger-safe front is standard for enclosed distribution boards.

Frequently asked questions

What is the breaking capacity of the A9N1P04DGN?

10,000 A Icn at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1.

What loads is the D curve on a 4 A MCB meant for?

The D curve trips magnetically at 10 to 14 times In (40 to 56 A), so it handles high inrush currents from small transformers, solenoid valves, or motor starters without nuisance tripping.

Where can I buy the A9N1P04DGN and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

MPN