The Schneider Electric A9N1P06CIN is a single-pole Acti9 xC60 miniature circuit breaker rated 6 A with a C-curve trip characteristic. It clips onto a standard 35 mm DIN rail in a distribution board or panel enclosure, occupying 18 mm width (2 x 9 mm pitches). The thermal-magnetic trip unit handles overloads and short-circuits; the C-curve means magnetic tripping occurs at 5 to 10 times In (here 8 x In ±20 % per the spec), so it suits mixed resistive and light inductive loads like general-purpose socket circuits, small lighting groups, and control transformers.
Rated 10 kA Icu at 220…240 V AC 50/60 Hz per IS/IEC 60947-2, 15 kA Icu at 12…48 V DC, and 6 kA Icu at 60 V DC. That 10 kA at 240 V is the standard interrupting rating for most residential and light commercial distribution boards in markets following IEC 60947-2. The limitation class is 3, meaning it lets through less fault energy than a Class 1 or 2 device — useful for protecting downstream equipment and reducing arc-flash stress on the panel.
Listed as current production (active lifecycle stage). This is a standard catalogue item in the Acti9 range, widely used across IEC markets. No obsolescence notice or last-time-buy window is in effect.
Installation notes for the panel builder
Tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible on the bottom; wire strip length 13 mm. Tightening torque 2 N·m. IP20 finger-safe front, so it's fine inside an enclosed panel but not for exposed or wet locations. The ON/OFF toggle gives local visual indication. Earth-leakage protection requires a separate residual current block (not integrated).