Schneider Electric A9N1P06DIN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P06DIN Acti9 xC60 MCB, 6 A, D Curve,

MPNA9N1P06DIN
Active

Schneider Electric Acti9 xC60, miniature circuit-breaker, A9N1P06DIN, 1P, 6 A, D curve, 10 kA Icu at 240 V AC, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P06DIN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P06DIN — Electrical & Protection
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 12...48 V DC 60 V DC
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P06DIN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P06DIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P06DIN — Approvals
ParameterValue
Conformity standardsIS/IEC 60947-2
A9N1P06DIN — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IS/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to IS/IEC 60947-2

Product details

The Schneider Electric A9N1P06DIN is a 1-pole miniature circuit-breaker from the Acti9 xC60 range, rated 6 A with a D tripping curve. The D curve means magnetic trip occurs at 12 x In (72 A) with a +/-20 % tolerance, sized for loads with high inrush such as small motor starters or transformer primaries.

Breaking capacity is 10 kA Icu at 220…240 V AC 50/60 Hz, 15 kA Icu at 12…48 V DC, and 6 kA Icu at 60 V DC, all per IS/IEC 60947-2. The limitation class is 3 per IS/IEC 60947-2, meaning it limits let-through energy enough to protect downstream wiring in a coordinated distribution scheme. Suitability for isolation is confirmed to the same standard — the toggle provides an air gap you can lock out.

Clip-on mounting to 35 mm DIN rail, 18 mm wide, 85 mm tall, 77.5 mm deep — fits a standard distribution board without overhang.

Frequently asked questions

What is the breaking capacity of A9N1P06DIN?

10 kA Icu at 220…240 V AC 50/60 Hz, 15 kA Icu at 12…48 V DC, and 6 kA Icu at 60 V DC, all per IS/IEC 60947-2.

What is the D curve magnetic trip threshold?

Magnetic tripping occurs at 12 x In (72 A for this 6 A breaker) with a +/-20 % tolerance, designed for loads with high inrush current.

Where can I buy A9N1P06DIN?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN
A9N1P06DIN