Skip to main content
Schneider Electric A9N1P10BGN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P10BGN Acti9 xC60 MCB, 10 A B Curve 1

MPNA9N1P10BGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, 1P, 10 A, B curve, 10 kA Icn at 240 V AC, IS/IEC 60898-1, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P10BGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P10BGN — Electrical & Protection
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P10BGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P10BGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P10BGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P10BGN is an Acti9 xC60 miniature circuit breaker — a single-pole thermal-magnetic MCB rated 10 A with a B curve and a breaking capacity of 10000 A Icn at 240 V AC 50/60 Hz, certified to IS/IEC 60898-1.

The 10 A rated current (In) sets the continuous load this MCB carries without tripping. The B curve means magnetic tripping occurs at 3 to 5 times In — 30 to 50 A — so it clears short-circuit faults fast but tolerates modest inrush from resistive or lighting loads. For distribution panels in commercial or light industrial buildings on 220...240 V AC networks, this covers most branch-circuit faults.

The 18 mm width (2 modules) fits compactly in a multi-way distribution board. IP20 rated — suitable for dry indoor panels only, not washdown or outdoor use.

Frequently asked questions

Where can I buy A9N1P10BGN?

The A9N1P10BGN is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is A9N1P10BGN's breaking capacity?

The A9N1P10BGN has a breaking capacity of 10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1.

What is the B curve on this MCB?

The B curve means magnetic tripping occurs at 3 to 5 times the rated current (30 to 50 A for this 10 A unit), providing fast short-circuit protection while allowing for moderate inrush from resistive or lighting loads.

MPN