Skip to main content
Schneider Electric A9N1P16DGN — 1-Pole MCB (DIN Rail)

Schneider A9N1P16DGN Acti9 xC60 MCB, 16 A, D Curve, 10 kA

MPNA9N1P16DGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, 1P, 16 A, D curve, 10 kA Icn at 240 V AC, 35 mm DIN rail, clip-on mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P16DGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P16DGN — Electrical & Protection
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P16DGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P16DGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P16DGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P16DGN is a 1-pole Acti9 xC60 miniature circuit breaker rated 16 A with a D tripping curve and a 10 kA breaking capacity at 240 V AC.

That's the range you want for loads with a high inrush: a 16 A motor drawing 100 A for a few cycles on start won't pop this breaker, but a hard fault will clear it fast. Thermal-magnetic trip technology means the bimetal strip handles the overload curve (slow, heat-based) while the solenoid handles short-circuit (instant, magnetic). The IP20 finger-safe terminals keep accidental contact out during commissioning.

Panel integration

Clip-on mount onto 35 mm DIN rail. Width is 18 mm (2 x 9 mm pitches), so it takes one modular space in the enclosure. Height 85 mm, depth 77.5 mm — fits standard distribution boards without crowding the gland plate. Tightening torque 2 N.m — no special tooling needed.

Frequently asked questions

Where can I buy the A9N1P16DGN?

We source the A9N1P16DGN to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9N1P16DGN?

The A9N1P16DGN has a 10 kA Icn breaking capacity at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1.

What does the D curve mean for this breaker?

The D curve sets magnetic tripping at 10 to 14 times the rated current (160–224 A for the 16 A version), making it suitable for loads with high inrush such as motors and transformers.

What compliance standards does the A9N1P16DGN meet?

The A9N1P16DGN is certified to IS/IEC 60898-1 and has tropicalisation level 2 per IEC 60068-1.

MPN
A9N1P16DGN