Schneider Electric A9N1P20CGN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P20CGN Acti9 xC60 MCB, 20A, 1P, C-Cur

MPNA9N1P20CGN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, 1P, 20 A, C-curve, 10 kA Icn at 240 V AC, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P20CGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P20CGN — Electrical & Protection
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P20CGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P20CGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P20CGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P20CGN is a 1-pole Acti9 xC60 miniature circuit breaker rated 20 A with a C-curve trip characteristic. It clips onto a 35 mm DIN rail and protects a single phase of a 220–240 V AC 50/60 Hz distribution circuit.

Breaking capacity and standard compliance

Rated breaking capacity is 10,000 A Icn at 240 V AC, certified to IS/IEC 60898-1. The limitation class is 3 per IS/IEC 60898-1, meaning it limits let-through energy enough to coordinate with downstream equipment in a well-designed panel.

Depth is 77.5 mm, height 85 mm — fits most enclosures with a 100 mm+ internal depth.

Frequently asked questions

What is the breaking capacity of A9N1P20CGN?

10,000 A Icn at 240 V AC 50/60 Hz, certified to IS/IEC 60898-1.

What is the C-curve trip range on this MCB?

Magnetic tripping operates between 5 and 10 times the rated current (100–200 A for this 20 A unit).

Where can I buy A9N1P20CGN and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What compliance standards does A9N1P20CGN meet?

It is certified to IS/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1 and pollution degree 3. IP20 rated for finger-safe terminals.