Skip to main content
Schneider Electric A9N1P25DGN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P25DGN Acti9 xC60 MCB, D Curve, 25 A,

MPNA9N1P25DGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P25DGN, D curve, 25 A, 1 pole, 10 kA breaking capacity, clip-on 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P25DGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P25DGN — Electrical & Protection
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P25DGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P25DGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P25DGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P25DGN is a 1-pole miniature circuit breaker from the Acti9 xC60 range, rated 25 A with a D tripping curve. The D curve means magnetic tripping between 10 and 14 times rated current. That curve suits loads with high inrush — motor starters, transformers, discharge lighting.

Breaking capacity is 10 kA Icn at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1. Thermal-magnetic trip unit — thermal element handles overloads (slow, I²t curve), magnetic coil handles short-circuits (instantaneous above the D-curve threshold). IP20 enclosure — fingersafe terminals but not sealed. Mount it inside a cabinet, not in a washdown zone.

What's on the nameplate

ON/OFF toggle with contact position indicator — green band visible when contacts are open. Local signalling is mechanical, no auxiliary contacts built in. Earth-leakage protection requires a separate block (Vigi or iC60 add-on). Electrical durability is 10,000 cycles; mechanical durability 20,000 cycles — plenty for a distribution board that sees a few operations a year.

Frequently asked questions

What is the breaking capacity of the A9N1P25DGN?

10,000 A Icn at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1.

MPN
A9N1P25DGN