The Schneider Electric A9N1P32CIN is a 1-pole Acti9 xC60 miniature circuit breaker with a 32 A rated current and C-curve trip characteristic, rated for distribution duty under IS/IEC 60947-2. Breaking capacity is 10 kA Icu at 220–240 V AC 50/60 Hz, 15 kA at 12–48 V DC, and 6 kA at 60 V DC, all per IS/IEC 60947-2. That 10 kA AC rating covers most secondary-distribution fault levels in standard Indian and IEC-based panels; the DC numbers matter for control-circuit or battery-backed loads. The thermal-magnetic trip unit gives overcurrent and short-circuit protection in one device — no separate fuse needed for the branch.
The Acti9 range is Schneider's standard residential and commercial MCB platform; the xC60 variant is the Indian-market version built to IS/IEC 60947-2. Compliance documentation — RoHS, REACH, and IEC test reports — is available from the manufacturer's document portal under the product range.
Integration notes
At 18 mm per pole, the A9N1P32CIN occupies two 9 mm DIN pitches. Depth of 77.5 mm and height of 85 mm fit standard 100 mm deep enclosures with gland-plate clearance.