Schneider Electric A9N1P40BIN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P40BIN Acti9 xC60 MCB, 1P 40A B-Curve

MPNA9N1P40BIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P40BIN, 1-pole, 40 A, B-curve, 10 kA breaking capacity at 240 V AC, clip-on DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P40BIN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P40BIN — Electrical & Protection
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 12...48 V DC 60 V DC
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P40BIN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)3.5 N.m
A9N1P40BIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P40BIN — Approvals
ParameterValue
Conformity standardsIS/IEC 60947-2
A9N1P40BIN — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IS/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to IS/IEC 60947-2

Product details

The Schneider Electric A9N1P40BIN is an Acti9 xC60 miniature circuit breaker — 1-pole, 40 A rated current, B-curve, with a 10 kA Icu breaking capacity at 240 V AC (IS/IEC 60947-2).

Width is 18 mm (2 x 9 mm pitches), so it occupies one module slot in a distribution board. The toggle actuator gives local ON/OFF indication. Strip length 13 mm, torque to 3.5 N·m.

Thermal-magnetic trip unit, 20,000 mechanical cycles, 10,000 electrical cycles. IP20 finger-safe terminals. Separate earth-leakage block can be added downstream if needed.

Frequently asked questions

What is A9N1P40BIN's breaking capacity at 240 V AC?

10 kA Icu at 220...240 V AC, 50/60 Hz, conforming to IS/IEC 60947-2.

MPN
A9N1P40BIN