Skip to main content
Schneider Electric A9N1P40CIN — 1-Pole MCB (DIN Rail)

A9N1P40CIN Acti9 MCB, 40 A, 1P, C-curve, 10 kA

MPNA9N1P40CIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, 1-pole, 40 A, C-curve, 10 kA Icu at 240 V AC, clip-on for 35 mm DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P40CIN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P40CIN — Electrical & Protection
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 12...48 V DC 60 V DC
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P40CIN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)3.5 N.m
A9N1P40CIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P40CIN — Approvals
ParameterValue
Conformity standardsIS/IEC 60947-2
A9N1P40CIN — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IS/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to IS/IEC 60947-2

Product details

The Schneider Electric A9N1P40CIN is a 40 A, 1-pole miniature circuit breaker from the Acti9 xC60 range, built to IS/IEC 60947-2. At 12–48 V DC it delivers 15 kA Icu, so it works in DC sub-distribution or control power feeds too.

Clip-on mounting to a 35 mm DIN rail, 18 mm wide (2 x 9 mm pitches), 85 mm tall, 77.5 mm deep. That 77.5 mm depth means it sits flush with most standard distribution boards — no extra clearance needed behind the rail. Strip length 13 mm, tighten to 3.5 N·m.

Frequently asked questions

How do I get current pricing and availability for A9N1P40CIN?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network — no online price or live count is displayed.

What is A9N1P40CIN's listed depth?

77.5 mm, which fits standard distribution board depths without extra rear clearance.

What standards does A9N1P40CIN comply with?

It conforms to IS/IEC 60947-2, with pollution degree 3, overvoltage category IV, and suitability for isolation per that standard.

MPN