Skip to main content
Schneider Electric A9N1P63BIN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P63BIN Acti9 xC60 MCB, 63 A, B Curve,

MPNA9N1P63BIN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, 1P, 63 A, B curve, 10 kA Icu at 240 V AC, clip-on 35 mm DIN rail, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N1P63BIN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P63BIN — Electrical & Protection
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 12...48 V DC 60 V DC
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P63BIN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)3.5 N.m
A9N1P63BIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P63BIN — Approvals
ParameterValue
Conformity standardsIS/IEC 60947-2
A9N1P63BIN — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IS/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to IS/IEC 60947-2

Product details

The A9N1P63BIN is a 1-pole Acti9 xC60 miniature circuit breaker rated 63 A with a B curve, meaning the magnetic trip threshold is 4 x In ±20 % — so it trips instantaneously between 200 A and 300 A. The 10 kA Icu at 220…240 V AC (IS/IEC 60947-2) tells you it can safely interrupt a fault current up to 10 kA without welding or rupturing; at 12…48 V DC the breaking capacity rises to 15 kA, and at 60 V DC it drops to 6 kA — so if you are using this on a DC bus, verify the fault current stays under the DC rating. The thermal-magnetic trip unit combines a bimetal for overload protection and a solenoid for short-circuit protection.

The IP20 finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible cable; strip 13 mm and tighten to 3.5 N·m. The bottom terminals are the biconnect / tunnel type, so you can daisy-chain outgoing feeders without extra junction blocks. The white housing carries a toggle actuator with ON/OFF local indication. The tropicalisation treatment (class 2 per IEC 60068-1) means the internal plastics resist humidity and fungal growth — relevant for panels in coastal or unconditioned plant environments.

Frequently asked questions

What is the breaking capacity of the A9N1P63BIN?

The A9N1P63BIN has a breaking capacity of 10 kA Icu at 220…240 V AC (50/60 Hz), 15 kA Icu at 12…48 V DC, and 6 kA Icu at 60 V DC, all per IS/IEC 60947-2.

Where can I buy the A9N1P63BIN?

The A9N1P63BIN is sourced and quoted to order against an RFQ through independent distribution; current pricing and availability are confirmed at quote time.

What standards does the A9N1P63BIN comply with?

It complies with IS/IEC 60947-2, with limitation class 3 and pollution degree 3.

MPN
A9N1P63BIN