The 6 kA Icn at 230 V AC (EN/IEC 60898-1) and 10 kA Icu at 230–240 V AC (IEC 60947-2) give it dual-standard coverage: the lower figure governs residential/similar installations, the higher figure covers industrial panel coordination. Both standards are listed on the nameplate, so the breaker qualifies for distribution boards and control panels alike.
Clip-on mounting to a DIN rail (35 mm symmetrical rail per EN 60715) and 18 mm width per pole — two 9 mm pitches — so this 1P+N unit occupies 18 mm of rail space. IP20 finger-safe protection is standard for enclosed distribution boards. The toggle provides local ON/OFF indication. Tropicalisation class 2 (IEC 60068-1) and pollution degree 3 (IEC 60947-2) mean it handles humid, dusty environments without derating — a common requirement for food-and-bev or HVAC plant rooms.