Schneider Electric A9N21493 — Residual Current Breakers (RCCB/RCBO)

Schneider A9N21493 Vigi TG40 40A 300mA Earth Leakage Block,

MPNA9N21493
Obsolete

Schneider Electric Prodis Vigi TG40 add-on residual current device, A9N21493, 3P+N, 40 A rated current, 300 mA sensitivity, Type AC, voltage-independent trip, DIN rail clip-on, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N21493 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationON/OFF indication
A9N21493 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)400 V AC 50 Hz phase to phase
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz conforming to EN 61009-1
Rated impulse withstand voltage (Uimp)6 kV conforming to EN 61009-1
Device location in systemGroup incomer
A9N21493 — Identification
ParameterValue
Product / component typeAdd-on residual current device
Product range / familyProdis
Device short nameVigi TG40
A9N21493 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules6
Terminal connectionsCable upstream 0.75...16 mm² rigid Cable upstream 0.33...10 mm² flexible
Wire stripping length13 mm
Terminal tightening torque2 N.m
Width54 mm
Height82 mm
Depth70 mm
A9N21493 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...60 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN 61009-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2 conforming to IEC 60068-1
A9N21493 — Approvals
ParameterValue
StandardsIEC 60947-2 EN 61009-1 EN 61009-2-1

Product details

The Schneider A9N21493 is a Prodis Vigi TG40 add-on residual current device — a 3P+N block rated 40 A with 300 mA earth-leakage sensitivity, Type AC, voltage-independent trip. Rated operational voltage is 400 V AC phase-to-phase at 50 Hz, with an insulation voltage of 400 V AC and impulse withstand of 6 kV per EN 61009-1. The 300 mA sensitivity is instantaneous — no time delay — so it clears ground faults immediately on detection. Pollution degree 3 and tropicalisation class 2 (per IEC 60068-1) qualify it for damp, non-condensing environments up to 95 % RH at 55 °C. Altitude limit is 2000 m.

Schneider has marked the A9N21493 as obsolete.

Screw terminals accept rigid cable 0.75…16 mm² or flexible 0.33…10 mm²; strip length 13 mm, torque to 2 N·m. Electrical connection to the upstream MCB is by screws — this is a mechanical and electrical add-on, not a standalone device. The 9 mm pitch occupies 6 pitches on the DIN rail. Local ON/OFF indication on the block face aids troubleshooting.

Designed to IEC 60947-2, EN 61009-1, and EN 61009-2-1. The voltage-independent trip mechanism ensures operation even if the neutral is lost upstream, a key reliability feature for group incomer protection.

Frequently asked questions

Where can I buy A9N21493?

The A9N21493 is sourced through independent distribution channels. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key ratings of A9N21493?

40 A rated current, 300 mA earth-leakage sensitivity, Type AC, voltage-independent trip, 400 V AC phase-to-phase, 6 kV impulse withstand, instantaneous trip, DIN rail clip-on, IP20.

What standards does A9N21493 comply with?

IEC 60947-2, EN 61009-1, and EN 61009-2-1. Pollution degree 3, tropicalisation class 2 per IEC 60068-1.

MPN