Certified protection for final distribution circuits
It provides overcurrent and short-circuit protection for single-phase final distribution circuits, wired as 1 pole + neutral (1P+N). The breaking capacity is 4500 A Icn at 230 V AC, 50/60 Hz, certified to EN/IEC 60898-1. The thermal-magnetic trip unit combines a bimetal strip for overload protection and a solenoid for short-circuit response.
Panel builders can plan for 18 mm per pole plus neutral — 36 mm total width for this 1P+N unit. Terminals accept flexible cable up to 10 mm² or rigid up to 16 mm², with a wire stripping length of 13 mm and a tightening torque of 2 N·m. The tunnel-type terminals are suitable for both upstream and downstream connections, simplifying wiring in a distribution board.