Breaking capacity is rated at 10 kA Icu at 230 V AC per IEC 60947-2 and 6000 A Icn per EN/IEC 60898-1. That dual-rating means the breaker is certified to both the industrial (60947-2) and residential/commercial (60898-1) standards, giving flexibility for specification across panel types.
Mounting is clip-on to a DIN rail, with tunnel-type terminals accepting 0.33...10 mm² flexible or 0.75...16 mm² rigid conductors upstream and downstream. The neutral is on the left, and the toggle provides local ON/OFF indication. IP20 finger protection is standard for enclosed panel use.