Breaking capacity is 10 kA Icu at 230 V AC per IEC 60947-2, and 6 kA Icn per EN/IEC 60898-1 — so it handles fault currents up to 10 kA at the panel voltage, which covers most residential and light commercial service entrances. The thermal-magnetic trip unit gives you an inverse-time overload curve plus instantaneous short-circuit protection.
Clip-on mounting to a DIN rail, 18 mm wide (2 x 9 mm pitches), 81 mm tall, 78 mm deep. Neutral on the left, toggle control, ON/OFF local indication. IP20 finger-safe front, so it's fine inside a standard distribution board or enclosure.
The A9N21561 is a standard catalog item in the Clario/iDPN family, widely specified for distribution boards.
Dual-rated to EN/IEC 60898-1 and EN/IEC 60947-2, so it's accepted for both household-type and industrial distribution applications. Pollution degree 3 per IEC 60947-1, tropicalisation class 2 per IEC 60068-1, limitation class 3 per EN/IEC 60898-1. Earth-leakage protection requires a separate block (not integrated).