The Schneider Electric A9N21562 is a Vigi TG60 add-on residual current device from the Prodis range, designed as a group incomer for AC networks. The 30 mA sensitivity is instantaneous (no time delay), so it trips immediately on a ground fault — appropriate for group incomer duty where you want fast disconnection, but check selectivity with downstream RCDs.
Schneider Electric lists the A9N21562 as obsolete. No official successor order code appears in the record.
Terminals accept 0.75…16 mm² rigid or 0.33…10 mm² flexible cable upstream; wire strip length 13 mm, tightening torque 2 N·m. IP20 finger-safe front, ON/OFF local indication. Ambient operating range -5…60 °C, storage -40…60 °C, altitude up to 2000 m.