Skip to main content
Schneider Electric A9N2P02CGN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P02CGN Acti9 xC60 MCB, 2A C-Curve 2P,

MPNA9N2P02CGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P02CGN, 2 A rated, C-curve, 2-pole, 10 kA breaking capacity per IS/IEC 60898-1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P02CGN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P02CGN — Electrical
ParameterValue
Rated current [In]2 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N2P02CGN — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Energy limitation class3 conforming to IS/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P02CGN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P02CGN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P02CGN — Approvals
ParameterValue
Standards / complianceIS/IEC 60898-1

Product details

The Schneider Electric A9N2P02CGN is an Acti9 xC60 miniature circuit breaker (MCB) rated 2 A with a C-curve trip characteristic, 2-pole configuration, and a breaking capacity of 10 kA at both 240 V and 415 V AC per IS/IEC 60898-1.

The 2 A rated current (In) and C-curve (magnetic trip 5–10 x In) mean this breaker protects circuits with moderate inrush loads — lighting banks, contactor coils, or small control transformers — without nuisance tripping on startup.

Frequently asked questions

Where can I buy A9N2P02CGN and how do I get a price?

The A9N2P02CGN is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is A9N2P02CGN's listed depth?

The A9N2P02CGN has a depth of 77.5 mm.

What is A9N2P02CGN's range?

The A9N2P02CGN belongs to the Acti9 range of miniature circuit breakers.

MPN