Skip to main content
Schneider Electric A9N2P02CIN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P02CIN Acti9 xC60 MCB, 2 A, C-Curve,

MPNA9N2P02CIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P02CIN, 2 A rated current, C-curve, 2 poles, 10 kA breaking capacity at 415 V AC, 77.5 mm depth, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P02CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P02CIN — Electrical
ParameterValue
Rated current [In]2 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9N2P02CIN — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity [Ics]6 kA conforming to IS/IEC 60947-2 - 100...125 V DC 7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz
Energy limitation class3 conforming to IS/IEC 60947-2
Suitable for isolationYes conforming to IS/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P02CIN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P02CIN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P02CIN — Approvals
ParameterValue
Standards / complianceIS/IEC 60947-2

Product details

The Schneider Electric A9N2P02CIN is a 2-pole miniature circuit breaker from the Acti9 xC60 series, rated at 2 A with a C-curve trip characteristic. The thermal-magnetic trip unit covers overload and short-circuit protection for a 2 A branch circuit in a distribution panel. Breaking capacity is 10 kA at 380–415 V AC (50/60 Hz) and 6 kA at 100–125 V DC, both per IS/IEC 60947-2.

Mounting and wiring notes

Strip length is 13 mm for top or bottom connection. The IP20 finger-safe terminals are fine for enclosed panels; keep it behind a door or cover. Local ON/OFF indication on the toggle lets you see the contact position at a glance. The white housing is standard for the Acti9 range — easy to spot in a crowded enclosure.

MPN
A9N2P02CIN