Schneider Electric A9N2P04DGN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P04DGN Acti9 xC60 MCB, D Curve, 4 A,

MPNA9N2P04DGN
Active

Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N2P04DGN, 2-pole, D curve, 4 A rated current, 10 kA breaking capacity, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P04DGN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P04DGN — Electrical
ParameterValue
Rated current [In]4 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N2P04DGN — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Energy limitation class3 conforming to IS/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P04DGN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P04DGN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P04DGN — Approvals
ParameterValue
Standards / complianceIS/IEC 60898-1

Product details

The Schneider Electric A9N2P04DGN is a 2-pole miniature circuit-breaker from the Acti9 xC60 series, rated 4 A with a D tripping curve.

Breaking capacity is 10 kA Icn at both 240 V and 415 V AC, 50/60 Hz, certified to IS/IEC 60898-1. Rated operational voltage covers 220...240 V AC and 380...415 V AC, so it handles single-phase and three-phase line-to-line connections within those ranges. Overvoltage category IV means it's rated for the mains supply entry point, not just downstream sub-distribution. Pollution degree 3 and tropicalisation class 2 (per IEC 60068-1) mean it tolerates conductive dust and high humidity — 95 % RH at 55 °C — so it holds up in non-air-conditioned industrial enclosures.

Frequently asked questions

What is the breaking capacity of the A9N2P04DGN?

10 kA Icn at both 240 V and 415 V AC, 50/60 Hz, per IS/IEC 60898-1.

What does the D curve mean on this MCB?

The magnetic trip operates at 10 to 14 times the rated current, so it is intended for loads with high inrush current like transformers or motor starters.

How do I get pricing and availability for the A9N2P04DGN?

Submit an RFQ — the part is sourced to order through independent distribution, with current pricing and availability confirmed at quote time.

MPN
A9N2P04DGN