Skip to main content
Schneider Electric A9N2P06DGN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P06DGN Acti9 xC60 MCB, D Curve, 6 A,

MPNA9N2P06DGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P06DGN, D curve, 6 A rated, 2-pole, 10 kA breaking capacity, clip-on 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N2P06DGN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P06DGN — Electrical
ParameterValue
Rated current [In]6 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N2P06DGN — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Energy limitation class3 conforming to IS/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P06DGN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P06DGN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P06DGN — Approvals
ParameterValue
Standards / complianceIS/IEC 60898-1

Product details

Breaking capacity is 10 kA Icn at both 240 V and 415 V AC, certified to IS/IEC 60898-1.

Occupies 4 x 9 mm pitches = 36 mm width, with a depth of 77.5 mm and height of 85 mm. Standard modular footprint for a 2P MCB fits any 36 mm-wide slot in a distribution board. Biconnect terminals on the bottom allow daisy-chaining or feed-through without additional connectors. IP20 finger-safe protection on the front.

Relative humidity tolerance is 95% at 55 °C. Overvoltage category IV, suitable for installation at the origin of the installation (utility side of the main distribution board). Earth-leakage protection requires a separate block (not integrated). Electrical and mechanical durability rated at 20,000 cycles each. ON/OFF indication via toggle position. White colour housing is standard for the Acti9 range.

Frequently asked questions

What is the D curve used for on this MCB?

The D curve (magnetic trip 10–14 x In) is designed for loads with high inrush currents — motors, transformers, welding equipment, or large capacitor banks — where a B or C curve would trip on startup surge.

What compliance documentation does Schneider provide for A9N2P06DGN?

The part is certified to IS/IEC 60898-1 and carries tropicalisation class 2 per IEC 60068-1. Standard Schneider documentation includes the declaration of conformity and test certificates available through their product support portal.

MPN
A9N2P06DGN