Skip to main content
Schneider Electric A9N2P10CGN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P10CGN Acti9 xC60 MCB, 10A C-Curve 2P

MPNA9N2P10CGN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, A9N2P10CGN, 10 A, C-curve, 2P, 10 kA Icn at 240 V AC, clip-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P10CGN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P10CGN — Electrical
ParameterValue
Rated current [In]10 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N2P10CGN — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Energy limitation class3 conforming to IS/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P10CGN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P10CGN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P10CGN — Approvals
ParameterValue
Standards / complianceIS/IEC 60898-1

Product details

The Schneider Electric A9N2P10CGN is a miniature circuit breaker from the Acti9 xC60 range, rated 10 A with a C-curve magnetic trip characteristic (5...10 x In) and 2 protected poles (2P).

The 10 kA Icn breaking capacity at 240 V AC (also rated 10 kA at 415 V AC) per IS/IEC 60898-1 tells you it can safely interrupt a fault current up to that level without welding contacts or rupturing the case, which is the standard for most final subcircuits in a distribution board. Rated operational voltage covers both 220...240 V AC and 380...415 V AC at 50/60 Hz, so it works across single-phase and three-phase line-to-neutral applications.

IP20 finger-safe front, so it's protected against accidental contact in a closed panel.

Durability and environment

Rated for 20,000 electrical and 20,000 mechanical cycles — typical for a distribution MCB in frequent-switching duty.

Frequently asked questions

What is A9N2P10CGN's breaking capacity?

10,000 A Icn at both 240 V AC and 415 V AC, 50/60 Hz, conforming to IS/IEC 60898-1.

What is the closest alternative to A9N2P10CGN in the Acti9 family?

Within the Acti9 xC60 range, the closest alternative would be a different current rating or pole configuration — the A9N2P10CGN is the specific 10 A, C-curve, 2-pole variant. No pin-compatible drop-in exists outside the same order code.

MPN