The A9N2P16CIN is a 2-pole miniature circuit breaker from the Acti9 xC60 series, rated 16 A with a C curve (magnetic trip at 8 x In ±20 %). The C curve suits general-purpose distribution loads — lighting, small motor circuits, and mixed resistive-inductive loads where inrush is moderate. The 10 kA breaking capacity at 380–415 V AC (IS/IEC 60947-2) means it can safely interrupt a fault current up to 10 kA without upstream cascading; at 100–125 V DC the Icu drops to 6 kA, so check DC fault levels if used in a DC sub-distribution board.
Schneider Electric A9N2P16CIN Acti9 xC60 MCB, 16 A, C Curve,
Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P16CIN, 2-pole, 16 A, C curve, 10 kA breaking capacity at 415 V AC, clip-on 35 mm DIN rail.
Specifications
| Parameter | Value |
|---|---|
| Product name | XC60 |
| Product range | Acti9 |
| Series / family | Acti9 |
| Device short name | xC60 |
| Product / component type | Miniature circuit-breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current [In] | 16 A |
| Number of protected poles | 2 |
| Pole configuration | 2P |
| Rated operational voltage [Ue] | 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC |
| Network type (AC/DC) | DC AC |
| Network frequency | 50/60 Hz |
| Parameter | Value |
|---|---|
| Tripping curve code | C |
| Magnetic tripping limit | 8 x In +/- 20 % |
| Breaking capacity (Icu) | 10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2 |
| Rated service breaking capacity [Ics] | 6 kA conforming to IS/IEC 60947-2 - 100...125 V DC 7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz |
| Energy limitation class | 3 conforming to IS/IEC 60947-2 |
| Suitable for isolation | Yes conforming to IS/IEC 60947-2 |
| Overvoltage category | IV |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Separate block |
| Operating / control type | Toggle |
| Mechanical durability (cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| 9 mm pitches | 4 |
| Width | 36 mm |
| Height | 85 mm |
| Depth | 77.5 mm |
| Mounting support | 35 mm DIN rail |
| Mounting mode | Clip-on |
| Terminal connections | Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom) |
| Terminal tightening torque | 2 N.m |
| Comb busbar / distribution block compatibility | Top: YES |
| Local signalling / indication | ON/OFF indication |
| Contact position indicator | Yes |
| Parameter | Value |
|---|---|
| Operating temperature range | -30...70 °C |
| Storage temperature range | -40...85 °C |
| Relative humidity | 95 % at 55 °C |
| Parameter | Value |
|---|---|
| Standards / compliance | IS/IEC 60947-2 |
Product details
Frequently asked questions
How do I get current pricing and availability for A9N2P16CIN?
Submit an RFQ through this listing. The part is sourced to order via independent distribution; pricing and stock levels are confirmed at quote time.
What is A9N2P16CIN's listed depth?
The depth is 77.5 mm. Combined with the 85 mm height and 36 mm width, it fits a standard 2-module DIN-rail footprint.
What compliance documentation does this brand provide for A9N2P16CIN?
The breaker carries IS/IEC 60947-2 certification and tropicalisation class 2 per IEC 60068-1. No RoHS or REACH declarations are in this record, but Schneider Electric typically provides those on request for the Acti9 range.