Skip to main content
Schneider Electric A9N2P16DGN

Schneider Electric A9N2P16DGN Acti9 xC60 MCB, 16 A, D Curve,

MPN A9N2P16DGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P16DGN, 2-pole, 16 A, D curve, 10 kA breaking capacity, 35 mm DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N2P16DGN key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...85 °C
Pollution degree3
ColorWhite

All specifications

A9N2P16DGN additional specifications
ParameterValue
Depth77.5 mm
Width36 mm
Height85 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The Schneider Electric A9N2P16DGN is a 2-pole miniature circuit breaker from the Acti9 xC60 range, rated 16 A with a D tripping curve and a breaking capacity of 10 kA at 240 V AC and also at 415 V AC per IS/IEC 60898-1. Rated operational voltage covers 220–240 V AC and 380–415 V AC at 50/60 Hz, so it handles standard single-phase and three-phase distribution panels. The thermal-magnetic trip unit gives you both overload protection (thermal bimetal) and short-circuit protection (magnetic coil) in one package.

Clip-on mounting on a 35 mm DIN rail, 36 mm wide (2 module spaces at 9 mm pitch = 4 pitches). Depth is 77.5 mm, height 85 mm — standard for the Acti9 family, so it slots into existing distribution boards without re-spacing.

The 20,000 electrical and 20,000 mechanical cycles give a solid service life for normal switching duty. Earth-leakage protection requires a separate block (not integrated), so if you need RCD functionality, add a compatible Acti9 vigi module downstream. The toggle switch gives local ON/OFF indication — useful for troubleshooting without a meter.

MPN