Skip to main content
Schneider Electric A9N2P32CGN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P32CGN Acti9 xC60 MCB, 32 A, C-Curve,

MPNA9N2P32CGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P32CGN, 32 A, C-curve, 2-pole, 10 kA breaking capacity at 240/415 V AC, clip-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P32CGN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P32CGN — Electrical
ParameterValue
Rated current [In]32 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N2P32CGN — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Energy limitation class3 conforming to IS/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P32CGN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P32CGN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P32CGN — Approvals
ParameterValue
Standards / complianceIS/IEC 60898-1

Product details

The Schneider Electric A9N2P32CGN is a 2-pole miniature circuit breaker from the Acti9 xC60 family, rated 32 A with a C-curve (magnetic trip between 5 and 10 times In). It breaks up to 10,000 A at 240 V AC and at 415 V AC, both per IS/IEC 60898-1 — so it handles residential and light commercial fault currents without cascading upstream.

Clip-on mounting on 35 mm DIN rail, 36 mm wide (4 x 9 mm pitches), 85 mm tall, 77.5 mm deep — standard panel footprint. Tightening torque 3.5 N·m. The white housing with ON/OFF toggle gives clear local indication.

Compliance and environment

Rated for overvoltage category IV, pollution degree 3, tropicalisation class 2 per IEC 60068-1, and 95 % relative humidity at 55 °C. Earth-leakage protection requires a separate block. Electrical durability 10,000 cycles, mechanical 20,000 cycles.

Frequently asked questions

What is the breaking capacity of A9N2P32CGN?

10,000 A Icn at both 240 V AC and 415 V AC, 50/60 Hz, per IS/IEC 60898-1.

What curve and trip range does this MCB have?

C-curve with magnetic tripping between 5 and 10 times the 32 A rated current.

How do I get current pricing and availability for A9N2P32CGN?

Submit an RFQ — the part is sourced to order through independent distribution, with availability and current pricing confirmed at quote time.

What compliance documentation does Schneider provide for A9N2P32CGN?

The breaker is certified to IS/IEC 60898-1 and tropicalised per IEC 60068-1 class 2. Overvoltage category IV, pollution degree 3.

MPN