Skip to main content
Schneider Electric A9N2P40DIN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P40DIN Acti9 xC60 MCB, 40 A D Curve 2

MPNA9N2P40DIN
Active

Schneider Electric Acti9 xC60, miniature circuit breaker, 40 A, D curve, 2P, 10 kA at 415 V AC, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P40DIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P40DIN — Electrical
ParameterValue
Rated current [In]40 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9N2P40DIN — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity [Ics]6 kA conforming to IS/IEC 60947-2 - 100...125 V DC 7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz
Energy limitation class3 conforming to IS/IEC 60947-2
Suitable for isolationYes conforming to IS/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P40DIN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P40DIN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P40DIN — Approvals
ParameterValue
Standards / complianceIS/IEC 60947-2

Product details

The Schneider Electric A9N2P40DIN is an Acti9 xC60 miniature circuit breaker rated at 40 A with a D curve, 2 poles, and a breaking capacity of 10 kA at 380–415 V AC (IS/IEC 60947-2).

Height 85 mm, depth 77.5 mm — fits standard distribution board cutouts. Biconnect bottom terminals allow daisy-chaining without additional busbars. IP20 finger-safe protection for panel-internal use.

Frequently asked questions

What is the breaking capacity of the A9N2P40DIN?

10 kA Icn at 380–415 V AC 50/60 Hz per IS/IEC 60947-2, and 6 kA Icu at 100–125 V DC per the same standard.

What does the D curve mean on this breaker?

The D curve sets the magnetic trip threshold at 12 x In ±20%, so the breaker tolerates high inrush currents typical of motor loads, transformers, or welding equipment without nuisance tripping.

Where can I buy the A9N2P40DIN?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
A9N2P40DIN