Skip to main content
Schneider Electric A9N60709 — 1-Pole MCB (DIN Rail)

Schneider Electric A9N60709 Acti9 C120 MCB, 1P C-curve 100 A

MPNA9N60709
Active

Schneider Electric Acti9 C120, miniature circuit-breaker, 1P, C-curve, 100 A, 5 kA Icu, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N60709 — Identification
ParameterValue
Product nameActi9 C120
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameC120a
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N60709 — Electrical & Protection
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)230...400 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)5 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N60709 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1 cable(s) 1...50 mm² rigid Tunnel type terminals1 cable(s) 1.5...35 mm² flexible
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Width27 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m top or bottom
A9N60709 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
A9N60709 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2
A9N60709 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9N60709 is a 1-pole Acti9 C120 miniature circuit-breaker rated for 100 A at 40 °C. It uses a thermal-magnetic trip unit with a C-curve — magnetic trip triggers at 8 x In ±20%, so it's sized for general-purpose distribution loads like lighting, small motor circuits, and mixed resistive-inductive panels where moderate inrush is expected. Breaking capacity is 5 kA Icu at 230...400 V AC, 50/60 Hz, certified to EN/IEC 60947-2. The limitation class is 3 per EN/IEC 60947-2, meaning it lets through less let-through energy than a class-1 breaker, which helps with downstream device coordination.

Takes 3 x 9 mm pitches of rail space — 27 mm wide. Tunnel terminals accept 1...50 mm² rigid or 1.5...35 mm² flexible cable. IP20 finger-safe front. Padlockable toggle for lockout/tagout.

Standards and environmental

Electrical durability 5000 cycles, mechanical 20000 cycles.

Frequently asked questions

What is the breaking capacity of A9N60709?

5 kA Icu at 230...400 V AC, 50/60 Hz, certified to EN/IEC 60947-2. That's the maximum fault current it can safely interrupt.

Where can I buy A9N60709 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the rated current of A9N60709?

100 A at 40 °C — that's the continuous current rating before thermal derating.

What standards does A9N60709 comply with?

EN/IEC 60947-2 — the industrial standard for circuit-breakers, covering both overload and short-circuit protection.

MPN
A9N60709