Specifications

A9N60733 — Identification
ParameterValue
Product nameActi9 C120
Series / familyActi9
Device short nameC120N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N60733 — Electrical
ParameterValue
Rated current [In]80 A at 40 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]230...400 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9N60733 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)10 kA Icu at 10 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA 75 % conforming to EN/IEC 60947-2 - 230...400 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - 250 V DC
Energy limitation class3 conforming to EN/IEC 60947-2
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N60733 — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
A9N60733 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
Relative humidity95 % at 55 °C
A9N60733 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

The Schneider Electric A9N60733 is an Acti9 C120N miniature circuit breaker (MCB) rated 80 A at 40 °C with a C-curve trip characteristic (magnetic trip at 8 x In ±20 %). That 80 A continuous rating means it carries the full load current of a distribution subfeed or a large commercial load without nuisance tripping — sized for a 3-phase 80 A feeder where you need thermal-magnetic protection in a 2-pole (2P) package. The 10 kA breaking capacity (Icu at 230…400 V AC, per EN/IEC 60947-2) tells you it can safely interrupt a fault current up to 10,000 A at the panelboard, which covers most commercial and light industrial service entrances. The C-curve is the standard choice for general distribution loads — motors, lighting, small transformers — where inrush is moderate and you want coordination downstream of a larger upstream device.

The 2-pole footprint takes 6 x 9 mm pitches (54 mm wide), so it occupies two module spaces on the rail. Tunnel-type terminals accept 1…50 mm² rigid or 1.5…35 mm² flexible cable; strip 15 mm and torque to 3.5 N·m. IP20 finger-safe terminals are fine for enclosed panels; keep the front cover on in service.

Limitation class 3 (energy-limiting) per that standard means it restricts let-through energy in a fault, which helps with downstream device coordination. The manufacturer provides the usual compliance documentation (declaration of conformity, CE marking) for the Acti9 range; specific RoHS/REACH declarations are available on request through the supply channel.

Frequently asked questions

What is the breaking capacity of the A9N60733?

10 kA Icu at 230…400 V AC 50/60 Hz, conforming to EN/IEC 60947-2. That's the maximum fault current it can safely interrupt at those voltages.

Where can I buy the A9N60733 and get current pricing?

The A9N60733 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the A9N60733's rated current and trip curve?

Rated 80 A at 40 °C with a C-curve trip characteristic (magnetic trip at 8 x In ±20 %). The C-curve suits general distribution loads with moderate inrush.

MPN
A9N60733