Skip to main content
Schneider Electric A9N60742 — Miniature Circuit Breakers (MCB)

Schneider Electric A9N60742 Acti9 C120N MCB, 100 A, 4P, C Cu

MPNA9N60742
Active

Schneider Electric Acti9 C120N, miniature circuit breaker, 4P, 100 A at 40 °C, C curve, 10 kA Icu at 230-400 V AC, thermal-magnetic trip, clip-on DIN rail.

$317.03Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N60742 — Identification
ParameterValue
Product nameActi9 C120
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N60742 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Number of protected poles4
Breaking capacity10 kA Icu at 10 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)7.5 kA 75 % conforming to EN/IEC 60947-2 - 230...400 V AC 50/60 Hz
Rated operational voltage (Ue)230...400 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
A9N60742 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Limitation class3 conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles
Mechanical durability (cycles)20000 cycles
A9N60742 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Wire stripping length15 mm
Local signalling/indicationON/OFF indication
Width108 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches12
A9N60742 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N60742 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The A9N60742 is a 4-pole miniature circuit breaker from the Schneider Acti9 C120 series, rated 100 A at 40 °C.

The 4-pole body occupies 12 x 9 mm pitches (108 mm wide). Tunnel-type terminals accept 1-50 mm² rigid or 1.5-35 mm² flexible cable; tighten to 3.5 N·m. The toggle handle is sealable in OFF or ON position with a 0.7 mm cable tie for lockout/tagout.

Durability and environmental ratings

Rated for 5000 electrical cycles and 20,000 mechanical cycles — enough for a distribution panel that sees infrequent switching; not a contactor replacement for daily cycling.

Frequently asked questions

How do I get current pricing and availability for A9N60742?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of A9N60742?

10 kA Icu at 230-400 V AC 50/60 Hz conforming to EN/IEC 60947-2. That is the maximum fault current it can safely interrupt at those voltages.

What compliance documentation does this brand provide for A9N60742?

The breaker is certified to EN/IEC 60947-2 (industrial MCB standard) and carries IP20 protection per IEC 60529. Tropicalisation class 2 per IEC 60068-1. Standard Schneider declarations for RoHS and REACH are available on request.

MPN