Skip to main content
Schneider Electric A9N60785 — Miniature Circuit Breakers (MCB)

Schneider Electric A9N60785 Acti9 C120H MCB, 80 A, 3P, C Cur

MPNA9N60785
Obsolete

Schneider Electric Acti9 C120H miniature circuit-breaker, A9N60785, 3-pole, 80 A, C curve, 15 kA breaking capacity per EN/IEC 60947-2, thermal-magnetic trip, clip-on 35 mm DIN rail.

$214.69Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N60785 — Identification
ParameterValue
Product nameActi9 C120
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N60785 — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration3P
Number of protected poles3
Breaking capacity15 kA Icu at 15 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)15 kA 100 % conforming to EN/IEC 60947-2 - 7.5 kA 50 % conforming to EN/IEC 60947-2 - 230...400 V AC 50/60 Hz
Rated operational voltage (Ue)230...400 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
A9N60785 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Limitation class3 conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles
Mechanical durability (cycles)20000 cycles
A9N60785 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Wire stripping length15 mm
Local signalling/indicationON/OFF indication
Width81 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches9
A9N60785 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N60785 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The A9N60785 is a 3-pole Acti9 C120H miniature circuit-breaker rated 80 A at 40 °C with a C curve (magnetic trip at 8 x In ±20 %). The 15 kA Icu breaking capacity at 230…400 V AC 50/60 Hz per EN/IEC 60947-2 means it can safely interrupt a fault current up to that level without upstream cascading — critical for coordination studies in distribution boards. Thermal-magnetic trip technology covers both overload (thermal bimetal) and short-circuit (solenoid) protection in one unit. IP20 finger-safe terminals accept up to 50 mm² rigid or 35 mm² flexible cable with tunnel-type terminals; tightening torque is 3.5 N·m. The 73 mm depth leaves clearance for cover-mounted accessories.

Designed for distribution applications in AC networks at 50/60 Hz. Rated operational voltage 230…400 V AC; rated insulation voltage 500 V AC. Electrical durability 5000 cycles, mechanical durability 20000 cycles. Earth-leakage protection via separate block (not integrated). Local ON/OFF indication on the toggle; handle sealable in OFF or ON position with 0.7 mm cable diameter lock.

Frequently asked questions

Where can I buy A9N60785 and how is it quoted?

The A9N60785 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of A9N60785?

80 A rated current at 40 °C, 3-pole, C curve, 15 kA Icu breaking capacity at 230…400 V AC, thermal-magnetic trip, clip-on 35 mm DIN rail.

What standards does A9N60785 comply with?

EN/IEC 60947-2 for miniature circuit-breakers, overvoltage category III, pollution degree 3, tropicalisation class 2 per IEC 60068-1, IP20 per IEC 60529.

MPN
A9N60785