Skip to main content
Schneider Electric A9N61658 — 2-Pole MCB (DIN Rail)

Schneider Electric A9N61658 C60PV-DC MCB, 13 A, 2P, Curve B,

MPNA9N61658
Active

Schneider Electric C60PV-DC series, A9N61658, miniature circuit breaker, 2-pole, 13 A, curve B, 800 V DC, 3 kA breaking capacity at 650 V DC.

$214.38Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9N61658 — Identification
ParameterValue
Product rangeC60
Device short nameC60PV-DC
Product / component typeMiniature circuit-breaker
A9N61658 — Electrical
ParameterValue
Rated current [In]13 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]800 V DC
Network type (AC/DC)DC
A9N61658 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit5.5 x In
Breaking capacity (Icu)3 kA Icu at 650 V DC 1.5 kA Icu at 800 V DC
Rated service breaking capacity [Ics]1.5 kA 100 % - 800 V DC 3 kA 100 % - 650 V DC
Suitable for isolationYes conforming to EN/IEC 60947-2
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N61658 — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height132.7 mm
Depth77.4 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel terminal (downside) 1...25 mm² rigid Tunnel terminal (downside) 1...16 mm² flexible Pre-wired cable (upside)
Terminal tightening torque2.5 N.m
Contact position indicatorYes
A9N61658 — Environmental
ParameterValue
Operating temperature range-25...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N61658 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

DC-rated MCB for photovoltaic and DC distribution

It is designed specifically for DC circuits up to 800 V DC, making it a fit for photovoltaic combiner boxes, DC distribution panels, and battery-bank protection where standard AC MCBs would not safely interrupt a DC arc. Breaking capacity is 3 kA Icu at 650 V DC and 1.5 kA Icu at 800 V DC — sufficient for most residential and small-commercial solar installations. Polarity insensitive: the C60PV-DC protects against bi-directional current, so no special wiring orientation is needed for string inverters or battery converters that may feed back.

Integration into a 35 mm DIN-rail panel

Occupies 8 x 9 mm pitches (72 mm width) for the 2-pole body. Depth is 77.4 mm, height 132.7 mm — fits within a standard 200 mm deep enclosure with room for wiring. The toggle control and padlocking in OFF position allow lockout/tagout without removing the breaker.

Utilisation category A (non-selectivity) per that standard. Rated insulation voltage (Ui) is 1000 V DC. Pollution degree 2. Relative humidity tolerance is 95 % at 55 °C.

Frequently asked questions

What is the breaking capacity of A9N61658 at 800 V DC?

The A9N61658 has a breaking capacity (Icu) of 1.5 kA at 800 V DC, and 3 kA at 650 V DC. The service breaking capacity (Ics) is 100 % of Icu at both voltages.

Does A9N61658 require polarity-sensitive wiring?

No. The C60PV-DC is polarity insensitive and protects against bi-directional current, so no special wiring orientation is needed.

MPN