The Schneider Electric A9P54310 is a 3-pole miniature circuit-breaker from the Acti9 iC40N line, rated 10 A with a C-curve trip characteristic. Breaking capacity is 10 kA Icu at 400 V AC per EN/IEC 60947-2, and 6 kA Icn at 400 V AC per EN/IEC 60898-1. That dual-rating means it's certified for both industrial (60947-2) and residential/ commercial (60898-1) applications — useful when a panel must meet both standards. The thermal-magnetic trip unit gives a magnetic tripping threshold of 5 to 10 times In (per 60898-1) and 8 x In ±20% (per 60947-2). For a 10 A breaker, that's roughly 50–100 A magnetic release, so it will hold moderate inrush from small motor or lighting loads without nuisance tripping.
Certified to EN/IEC 60898-1 and EN/IEC 60947-2, with quality marks AENOR and OVE.